filtering technology

 

Filtration of feedwater in power stations

 

The filtration of feedwater is extremely important in the technology process of power stations. At the critical points of the water-steam cycle the iron and iron oxide pollutions get into the system. These pollutions may cause malfunctions in other points of the process, mainly in valves, nozzles and devices. The failures may prevent or undermine the continuous operation of a power station block. During the cleaning of the filter the system must be switched over to other mode or even stopped in worst cases. None of them is a preferred event. Should it happen that the free surface of the filter and its capacity do not comply with the concentration of pollution or the filter grade size does not comply with the polluting particle size distribution, the unwanted event may occur.

 

Further the selection of a concrete filter; its applied method as well as the operational experience will be presented.

 

1.,     Input data
The filtered medium is feedwater, its temperature 130-250 °C, pressure 50-290 bar. The flow rate 24 t/hour with the minimum 20 t/hour. It should be mentioned that the original filter had to be serviced (replaced or cleaned) in every 50 working hours.

Figure 1.   The original filter. (D50 x 100 mm)

Figure 1.

 

 2.,     Laboratory tests 

On the basis of the samples taken from the feedwater the polluting materials, their chemical analysis, particle sizes, concentrations and quantity of the characteristic fractions were determined.

The samples were taken from the feedwater reservoirs and after the magnetic filter. The results are showed in Figure 2.

Figure 2.

From the diagram it can be concluded that the particle sizes are above 100 μm in all three cases (almost 90% of them). Only the magnetic filter samples are worse, the 17% of particles are below 100 μm.
Then the chemical analysis of water followed. The results are shown in Figure 3.

Figure 3.

The vertical axis is the years, the horizontal one is the total iron content. Different colours illustrate the iron content of waters flowing into the feedwater. The diagram shows that the concentration of pollution varies. In spite of it the minimum and maximum concentrations can be well estimated. In all probability the concentration falls between 100 and 200 mg/m3.

3.,     Fixing the filter objective
The laboratory tests proved a 100 μm filter can remove 83 – 90% of the 100 - 200 mg/m3 pollution. The fluctuation of the concentration is near to 100% so it is reasonable to select a large free surface. When fixing the filter objective, some tests must be done on the required free surface. Our aim was to extend the 50-hour service cycle to quarterly one.
Figure 4 shows the test results.

Figure 4.

The horizontal axis is the number of operating hours, the vertical one is the water flow that passed through the filter. The black line is for the original, small free surface 205 μm filter, which required 50-hour service cycle. The red line is for 2 Ecofilt Mikrofilters with 250 μm filter grade size and much larger free surface. This equipment worked 750 hours. The third green line is for 100 μm filters, selected on the basis of laboratory results. Four filters worked 1250 hours in parallel connection. Evaluation of test results made possible to fix the filter objective. The 100 μm filter grade size is suitable, because it is not harmful for the equipment to be protected. On the other hand, the free surface of the filter must be 1000 times larger than that of the original in order to ensure the long service cycle. Now the filter objective is to install a battery of 100 μm filters with quarterly service cycle.

4.,     Implementation
 A battery of filters were designed. It has two filter housings in parallel connection. In each housing there are 4 filter cartridges. With help of valves a branch can be chosen so the uninterruptible operation is possible. The service is required quarterly, because the nominal operating time of the filters  is 1300 hours. Figure 5 shows a 3D picture of the filter battery, whilst Figure 6 shows the filter cartridges. (Size D90 x 600 mm)

 

Figure 5.                                               Figure 6.

The first filter was started just after the installation. For continuous monitoring of clogging a ∆p transmitter was also mounted. Figure 7 shows a diagram of pressure drop versus time. The horizontal axis is the operating time, the vertical one is the pressure drop.

Figure 7.

As it can be seen the starting pressure drop of filter is 20 millibar, during the operation the pressure drop increased up to the 1.72 bar, at that level the filter was stopped. This value was reached after 812 hours of operation and filtering 27650 tons of feedwater.

5.,     Installation and its results
In 4 years the result of development was implemented at each block of power station. The unexpected failures have been eliminated, the preventive maintenance of filters can be well planned. Earlier the unexpected breakdowns stopped the electric energy generation of blocks and because of this the power station company paid heavy (sometimes many tens of thousand EUR). The project was successful, the preventive maintenance and service can be planned after the installation of the new filter batteries. The unexpected breakdowns were eliminated and the “lost” penalties recovered the expenses of this installation in a few couples of workday at each block.        

Technical data of filters:

Type:  Ecofilt Mikrofilter
Manufacturer:  Marketinfo
Medium to filter:  feedwater
Capacity:  20 - 34 t/h
Operating temperature:  130 - 250 °C
Operating pressure:  50 - 290 bar
No. of cartridges:  4 db
Size of cartridges:  D90 x 600 mm
Maximum ∆p:  50 bar
Max. operating pressure:  max. 300 bar
Filter grade size:   100 μm
Material:  stainless steel

The first filter has been working since 1999, it works together with the others installed later even today. 

Acknowledgement: I would like to express my acknowledgements to the management and workers of the power station for the opportunity of tests and this project as well as for the correct co-operation.

Back to the News
 

filtering technology